0.6/1kV NA2XBY Al/XLPE/STA/PVC Armoured Underground Power Cable
Introduction of NA2XBY Al/XLPE/STA/PVC Armoured Underground Power Cable
XLPE insulated power cables for rated voltages up to 0.6/1 kV are fit for AC 50Hz distribution lines for the same rated voltages. The mechanical and electrical properties of these cables are accordant with GB/T12706—2008 ( Power
cables extruded insulation and their accessories of rated voltagesl kV(Umz1.2kV)up to ) and IEC-60502—1 :2004 ( Extruded insulation power cables and appendites for rated voltages 1kV up to 30kV)
Instruction of Application
1. Rated Voltage: 0.6/1kV
2. Max.permissible operating temperature of conductor is 90℃.
3. Conductor short-circuit temperature shall not exceed 250℃ Max. sustaining period shall not exceed 5 seconds.
4. Bending Radius
Bending radius of single core cable:20(D+d)±5%
Bending radius of multi core cable:15(D+d)±5%
D-Actual outer diameter of cable sample(mm);
d-Actual diameter of the conductor(mm).
5. No restriction of level difference along the route for installation.
6. Installation temperature shall be heated when ambient temperature is below 0℃
Production Range of XLPE Insulated Power Cable
Type | Description | Scope of Application |
YJV YJLV Z(K)-YJV Z(K)-YJLV | Cu or AI conductor XLPE insulated PVC sheathed power cable | Installed indoors or outdoors. In case unable to bear external mechanical forces but tractive force during laying, single core cable in magnetic duct is not permissible. |
YJV22 YJLV22 Z(K)-YJV22 Z(K)-YJLV22 | Cu or AI Conductor XLPE Insulated PVC Sheathed Steel Tape Armoured Power Cable | For laying in ground able to bear external mechanical forces, but unable to bear large pulling force. |
YJV32 YJLV32 Z(K)-YJV32 Z(K)-YJLV32 | Cu or AI Conductor XLPE Insulated PVC Sheathed Fine Steel Wire Armoured Power Cable | For laying in water or able to bear external mechanical forces and equal pulling force. |
Structure of NA2XY Aluminum Conductor XLPE Insulation Power Cable
The main technique performance of NA2XBY Al/XLPE/STA/PVC Armoured Underground Power Cable
Maximum DC resistance of cable conductor at 20℃
Rated cross area(mm2) | 0.5 | 0.75 | 1.0 | 1.5 | 2.5 | 4 | 6 | 10 | |
Cu(Ω/km) | Non tinned | 36.0 | 24.5 | 18.1 | 12.1 | 7.41 | 4.61 | 3.08 | 1.83 |
Tinned | 36.7 | 24.8 | 18.2 | 12.2 | 7.56 | 4.70 | 3.11 | 1.84 | |
Al (Ω/km) | / | / | / | 18.1 | 12.1 | 7.41 | 4.61 | 3.08 | |
Rated cross area(mm2) | 16 | 25 | 35 | 50 | 70 | 95 | 120 | 150 | |
Cu (Ω/km) | Non tinned | 1.15 | 0.727 | 0.524 | 0.387 | 0.268 | 0.193 | 0.153 | 0.124 |
Tinned | 1.16 | 0.734 | 0.529 | 0.391 | 0.270 | 0.195 | 0.154 | 0.126 | |
Al (Ω/km) | 1.91 | 1.20 | 0.868 | 0.641 | 0.443 | 0.320 | 0.253 | 0.206 | |
Rated cross area(mm2) | 185 | 240 | 300 | 400 | 500 | 630 | 800 | 1000 | |
Cu (Ω/km) | Non tinned | 0.0991 | 0.0754 | 0.0601 | 0.0470 | 0.0366 | 0.0283 | 0.0221 | 0.0176 |
Tinned | 0.100 | 0.0762 | 0.0607 | 0.0475 | 0.0369 | 0.0286 | 0.0224 | 0.0177 | |
Al ( Ω/km) | 0.164 | 0.125 | 0.100 | 0.0778 | 0.0605 | 0.0469 | 0.0367 | 0.0291 |
Approximate size & weight of NA2XBY Al/XLPE/STA/PVC Armoured Underground Power Cable
Two-core of NA2XBY Al/XLPE/STA/PVC Armoured Underground Power Cable
Normal cross-sectional area of conductor | Normal thickness of insulation | Thickness of inner-covering | Thickness of steel tape | Normal thickness of sheath | Approx. overall diameter | Approx. weight |
mm² | mm | mm | mm | mm | mm | kg/km |
2*4 | 0.7 | 1.2 | 0.2 | 1.8 | 15 | 274 |
2*6 | 0.7 | 1.2 | 0.2 | 1.8 | 16 | 314 |
2*10 | 0.7 | 1.2 | 0.2 | 1.8 | 18 | 396 |
2*16 | 0.7 | 1.2 | 0.2 | 1.8 | 20 | 490 |
2*25 | 0.9 | 1.2 | 0.2 | 1.8 | 24 | 645 |
2*35 | 0.9 | 1.2 | 0.2 | 1.8 | 26 | 782 |
2*50 | 1.0 | 1.2 | 0.2 | 1.8 | 24 | 775 |
2*70 | 1.1 | 1.2 | 0.5 | 2.0 | 28 | 1263 |
2*95 | 1.1 | 1.2 | 0.5 | 2.1 | 31 | 1532 |
2*120 | 1.2 | 1.2 | 0.5 | 2.2 | 34 | 1783 |
2*150 | 1.4 | 1.3 | 0.5 | 2.4 | 37 | 2113 |
2*185 | 1.6 | 1.3 | 0.5 | 2.5 | 41 | 2508 |
Three-core of NA2XBY Al/XLPE/STA/PVC Armoured Underground Power Cable
Normal cross-sectional area of conductor | Normal thickness of insulation | Thickness of inner-covering | Thickness of steel tape | Normal thickness of sheath | Approx. overall diameter | Approx. weight |
mm² | mm | mm | mm | mm | mm | kg/km |
3*4 | 0.7 | 1.2 | 0.2 | 1.8 | 15 | 303 |
3*6 | 0.7 | 1.2 | 0.2 | 1.8 | 16 | 352 |
3*10 | 0.7 | 1.2 | 0.2 | 1.8 | 19 | 462 |
3*16 | 0.7 | 1.2 | 0.2 | 1.8 | 21 | 582 |
3*25 | 0.9 | 1.2 | 0.2 | 1.8 | 25 | 766 |
3*35 | 0.9 | 1.2 | 0.2 | 1.8 | 28 | 927 |
3*50 | 1.0 | 1.2 | 0.2 | 1.9 | 28 | 1027 |
3*70 | 1.1 | 1.2 | 0.5 | 2.0 | 33 | 1636 |
3*95 | 1.1 | 1.2 | 0.5 | 2.2 | 36 | 2026 |
3*120 | 1.2 | 1.3 | 0.5 | 2.3 | 39 | 2394 |
3*150 | 1.4 | 1.3 | 0.5 | 2.4 | 43 | 2832 |
3*185 | 1.6 | 1.4 | 0.5 | 2.6 | 48 | 3400 |
3*240 | 1.7 | 1.5 | 0.5 | 2.8 | 53 | 4195 |
3*300 | 1.8 | 1.5 | 0.5 | 2.9 | 58 | 5020 |
3+1 core of NA2XBY Al/XLPE/STA/PVC Armoured Underground Power Cable
Normal cross-sectional area of conductor | Normal thickness of insulation | Thickness of inner-covering | Thickness of steel tape | Normal thickness of sheath | Approx. overall diameter | Approx. weight |
mm² | mm | mm | mm | mm | mm | kg/km |
3*4+1*2.5 | 0.7 | 1.2 | 0.2 | 1.8 | 16 | 333 |
3*6+1*4 | 0.7 | 1.2 | 0.2 | 1.8 | 17 | 388 |
3*10+1*6 | 0.7 | 1.2 | 0.2 | 1.8 | 20 | 503 |
3*16+1*10 | 0.7 | 1.2 | 0.2 | 1.8 | 23 | 650 |
3*25+1*16 | 0.9 | 1.2 | 0.2 | 1.8 | 26 | 856 |
3*35+1*16 | 0.9 | 1.2 | 0.2 | 1.8 | 28 | 994 |
3*50+1*25 | 1.0 | 1.2 | 0.2 | 1.9 | 30 | 1175 |
3*70+1*35 | 1.1 | 1.2 | 0.2 | 2.1 | 35 | 1872 |
3*95+1*50 | 1.1 | 1.2 | 0.2 | 2.2 | 39 | 2303 |
3*120+1*70 | 1.2 | 1.3 | 0.2 | 2.3 | 43 | 2772 |
3*150+1*70 | 1.4 | 1.4 | 0.5 | 2.5 | 47 | 3238 |
3*185+1*95 | 1.6 | 1.5 | 0.5 | 2.6 | 52 | 3908 |
3*240+1*120 | 1.7 | 1.6 | 0.5 | 2.8 | 57 | 4792 |
3*300+1*150 | 1.8 | 1.7 | 0.5 | 3 | 63 | 5747 |
Four-core of NA2XBY Al/XLPE/STA/PVC Armoured Underground Power Cable
Normal cross-sectional area of conductor | Normal thickness of insulation | Thickness of inner-covering | Thickness of steel tape | Normal thickness of sheath | Approx. overall diameter | Approx. weight |
mm² | mm | mm | mm | mm | mm | kg/km |
4*4 | 0.7 | 1.2 | 0.2 | 1.8 | 16 | 408 |
4*6 | 0.7 | 1.2 | 0.2 | 1.8 | 17 | 488 |
4*10 | 0.7 | 1.2 | 0.2 | 1.8 | 21 | 688 |
4*16 | 0.7 | 1.2 | 0.2 | 1.8 | 23 | 927 |
4*25 | 0.9 | 1.2 | 0.2 | 1.8 | 27 | 1267 |
4*35 | 0.9 | 1.2 | 0.2 | 1.8 | 30 | 1558 |
4*50 | 1.0 | 1.2 | 0.2 | 2.0 | 33 | 2136 |
4*70 | 1.1 | 1.2 | 0.5 | 2.1 | 36 | 2485 |
4*95 | 1.1 | 1.2 | 0.5 | 2.3 | 41 | 2813 |
4*120 | 1.2 | 1.3 | 0.5 | 2.4 | 44 | 2945 |
4*150 | 1.4 | 1.4 | 0.5 | 2.4 | 49 | 3533 |
4*185 | 1.6 | 1.5 | 0.5 | 2.7 | 54 | 4236 |
4*240 | 1.7 | 1.6 | 0.5 | 3.0 | 60 | 5625 |
4*300 | 1.8 | 1.7 | 0.5 | 3.1 | 66 | 6286 |
3+2 core of NA2XBY Al/XLPE/STA/PVC Armoured Underground Power Cable
Normal cross-sectional area of conductor | Normal thickness of insulation | Thickness of inner-covering | Thickness of steel tape | Normal thickness of sheath | Approx. overall diameter | Approx. weight |
mm² | mm | mm | mm | mm | mm | kg/km |
3*4+2*1.5 | 0.7 | 1.2 | 0.2 | 1.8 | 17 | 356 |
3*6+2*4 | 0.7 | 1.2 | 0.2 | 1.8 | 18 | 420 |
3*10+2*6 | 0.7 | 1.2 | 0.2 | 1.8 | 21 | 538 |
3*16+2*10 | 0.7 | 1.2 | 0.2 | 1.8 | 24 | 702 |
3*25+2*16 | 0.9 | 1.2 | 0.2 | 1.8 | 27 | 930 |
3*35+2*16 | 0.9 | 1.2 | 0.2 | 1.8 | 29 | 1061 |
3*50+2*25 | 1.0 | 1.2 | 0.5 | 2.0 | 35 | 1770 |
3*70+2*35 | 1.1 | 1.2 | 0.5 | 2.1 | 40 | 2244 |
3*95+2*50 | 1.1 | 1.2 | 0.5 | 2.3 | 44 | 2769 |
3*120+2*70 | 1.2 | 1.3 | 0.5 | 2.4 | 49 | 3269 |
3*150+2*70 | 1.4 | 1.4 | 0.5 | 2.5 | 53 | 3752 |
3*185+2*95 | 1.6 | 1.5 | 0.5 | 2.7 | 59 | 4565 |
3*240+2*120 | 1.7 | 1.6 | 0.5 | 2.9 | 65 | 5635 |
3*300+2*150 | 1.8 | 1.7 | 0.5 | 3.1 | 72 | 6783 |
4+1 core of NA2XBY Al/XLPE/STA/PVC Armoured Underground Power Cable
Normal cross-sectional area of conductor | Normal thickness of insulation | Thickness of inner-covering | Thickness of steel tape | Normal thickness of sheath | Approx. overall diameter | Approx. weight |
mm² | mm | mm | mm | mm | mm | kg/km |
4*4+1*2.5 | 0.7 | 1.2 | 0.2 | 1.8 | 17 | 368 |
4*6+1*4 | 0.7 | 1.2 | 0.2 | 1.8 | 18 | 460 |
4*10+1*6 | 0.7 | 1.2 | 0.2 | 1.8 | 21 | 588 |
4*16+1*10 | 0.7 | 1.2 | 0.2 | 1.8 | 24 | 738 |
4*25+1*16 | 0.9 | 1.2 | 0.2 | 1.8 | 28 | 976 |
4*35+1*16 | 0.9 | 1.2 | 0.2 | 1.8 | 30 | 1169 |
4*50+1*25 | 1.0 | 1.2 | 0.5 | 2.1 | 36 | 1191 |
4*70+1*35 | 1.1 | 1.2 | 0.5 | 2.2 | 41 | 2432 |
4*95+1*50 | 1.1 | 1.2 | 0.5 | 2.3 | 46 | 3004 |
4*120+1*70 | 1.2 | 1.3 | 0.5 | 2.5 | 51 | 3679 |
4*150+1*70 | 1.4 | 1.4 | 0.5 | 2.6 | 55 | 4126 |
4*185+1*95 | 1.6 | 1.5 | 0.5 | 2.8 | 61 | 5029 |
4*240+1*120 | 1.7 | 1.6 | 0.5 | 2.9 | 69 | 6288 |
4*300+1*150 | 1.8 | 1.8 | 0.5 | 3.3 | 76 | 7552 |
5 core of NA2XBY Al/XLPE/STA/PVC Armoured Underground Power Cable
Normal cross-sectional area of conductor | Normal thickness of insulation | Thickness of inner-covering | Thickness of steel tape | Normal thickness of sheath | Approx. overall diameter | Approx. weight |
mm² | mm | mm | mm | mm | mm | kg/km |
5*4 | 0.7 | 1.2 | 0.2 | 1.8 | 17 | 380 |
5*6 | 0.7 | 1.2 | 0.2 | 1.8 | 19 | 448 |
5*10 | 0.7 | 1.2 | 0.2 | 1.8 | 22 | 605 |
5*16 | 0.7 | 1.2 | 0.2 | 1.8 | 25 | 769 |
5*25 | 0.9 | 1.2 | 0.5 | 1.8 | 28 | 1023 |
5*35 | 0.9 | 1.2 | 0.5 | 2.0 | 33 | 1603 |
5*50 | 1.0 | 1.2 | 0.5 | 2.1 | 37 | 2033 |
5*70 | 1.1 | 1.2 | 0.5 | 2.2 | 42 | 2578 |
5*95 | 1.1 | 1.3 | 0.5 | 2.4 | 48 | 3265 |
5*120 | 1.2 | 1.4 | 0.5 | 2.6 | 53 | 3797 |
5*150 | 1.4 | 1.5 | 0.5 | 2.7 | 58 | 4565 |
5*185 | 1.6 | 1.6 | 0.5 | 2.9 | 65 | 5494 |
5*240 | 1.7 | 1.7 | 0.5 | 3.2 | 73 | 6981 |
5*300 | 1.8 | 1.9 | 0.5 | 3.4 | 80 | 8341 |
The power cable current capacity of 0.6/1kV NA2XBY Al/XLPE/STA/PVC Armoured Underground Power Cable
Apply the model number: YJV22(N2XBY) YJLV22(NA2XBY)
Limit the term:Environment temperature:400C;: Soil temperature:250C; Soil thermal receptivity: 2000C·cm/W
Conductor Area mm2 | The long-term admission current-carrying capacity in air(A) | The long-term admission current-carrying capacity in soil(A) | ||||||
Copper core cable | Aluminum core cable | Copper core cable | Aluminum core cable | |||||
1-core | 3 or 4 core | 1-core | 3 or 4 core | 1-core | 3 or 4 core | 1-core | 3 or 4 core | |
2.5 | 34 | 32 | 27 | 25 | 36 | 32 | 27 | 25 |
4 | 44 | 41 | 35 | 32 | 47 | 41 | 35 | 32 |
6 | 56 | 52 | 45 | 42 | 59 | 52 | 46 | 42 |
10 | 77 | 70 | 60 | 53 | 78 | 69 | 59 | 53 |
16 | 100 | 91 | 78 | 70 | 102 | 90 | 77 | 71 |
25 | 132 | 118 | 102 | 91 | 130 | 117 | 104 | 91 |
35 | 164 | 150 | 127 | 114 | 169 | 143 | 117 | 113 |
50 | 196 | 182 | 152 | 146 | 187 | 169 | 139 | 134 |
70 | 251 | 228 | 195 | 178 | 226 | 208 | 174 | 165 |
95 | 305 | 273 | 236 | 214 | 269 | 247 | 208 | 195 |
120 | 351 | 314 | 272 | 246 | 300 | 282 | 239 | 221 |
150 | 401 | 360 | 311 | 278 | 339 | 321 | 269 | 247 |
185 | 461 | 410 | 359 | 319 | 382 | 356 | 300 | 278 |
240 | 546 | 483 | 424 | 378 | 435 | 408 | 348 | 321 |
300 | 611 | 552 | 474 | 419 | 495 | 469 | 391 | 365 |
400 | 716 | / | 546 | / | 574 | / | 456 | / |
0.6/1kV NA2XBY Al/XLPE/STA/PVC Armoured Underground Power Cable
Introduction of NA2XBY Al/XLPE/STA/PVC Armoured Underground Power Cable
XLPE insulated power cables for rated voltages up to 0.6/1 kV are fit for AC 50Hz distribution lines for the same rated voltages. The mechanical and electrical properties of these cables are accordant with GB/T12706—2008 ( Power
cables extruded insulation and their accessories of rated voltagesl kV(Umz1.2kV)up to ) and IEC-60502—1 :2004 ( Extruded insulation power cables and appendites for rated voltages 1kV up to 30kV)
Instruction of Application
1. Rated Voltage: 0.6/1kV
2. Max.permissible operating temperature of conductor is 90℃.
3. Conductor short-circuit temperature shall not exceed 250℃ Max. sustaining period shall not exceed 5 seconds.
4. Bending Radius
Bending radius of single core cable:20(D+d)±5%
Bending radius of multi core cable:15(D+d)±5%
D-Actual outer diameter of cable sample(mm);
d-Actual diameter of the conductor(mm).
5. No restriction of level difference along the route for installation.
6. Installation temperature shall be heated when ambient temperature is below 0℃
Production Range of XLPE Insulated Power Cable
Type | Description | Scope of Application |
YJV YJLV Z(K)-YJV Z(K)-YJLV | Cu or AI conductor XLPE insulated PVC sheathed power cable | Installed indoors or outdoors. In case unable to bear external mechanical forces but tractive force during laying, single core cable in magnetic duct is not permissible. |
YJV22 YJLV22 Z(K)-YJV22 Z(K)-YJLV22 | Cu or AI Conductor XLPE Insulated PVC Sheathed Steel Tape Armoured Power Cable | For laying in ground able to bear external mechanical forces, but unable to bear large pulling force. |
YJV32 YJLV32 Z(K)-YJV32 Z(K)-YJLV32 | Cu or AI Conductor XLPE Insulated PVC Sheathed Fine Steel Wire Armoured Power Cable | For laying in water or able to bear external mechanical forces and equal pulling force. |
Structure of NA2XY Aluminum Conductor XLPE Insulation Power Cable
The main technique performance of NA2XBY Al/XLPE/STA/PVC Armoured Underground Power Cable
Maximum DC resistance of cable conductor at 20℃
Rated cross area(mm2) | 0.5 | 0.75 | 1.0 | 1.5 | 2.5 | 4 | 6 | 10 | |
Cu(Ω/km) | Non tinned | 36.0 | 24.5 | 18.1 | 12.1 | 7.41 | 4.61 | 3.08 | 1.83 |
Tinned | 36.7 | 24.8 | 18.2 | 12.2 | 7.56 | 4.70 | 3.11 | 1.84 | |
Al (Ω/km) | / | / | / | 18.1 | 12.1 | 7.41 | 4.61 | 3.08 | |
Rated cross area(mm2) | 16 | 25 | 35 | 50 | 70 | 95 | 120 | 150 | |
Cu (Ω/km) | Non tinned | 1.15 | 0.727 | 0.524 | 0.387 | 0.268 | 0.193 | 0.153 | 0.124 |
Tinned | 1.16 | 0.734 | 0.529 | 0.391 | 0.270 | 0.195 | 0.154 | 0.126 | |
Al (Ω/km) | 1.91 | 1.20 | 0.868 | 0.641 | 0.443 | 0.320 | 0.253 | 0.206 | |
Rated cross area(mm2) | 185 | 240 | 300 | 400 | 500 | 630 | 800 | 1000 | |
Cu (Ω/km) | Non tinned | 0.0991 | 0.0754 | 0.0601 | 0.0470 | 0.0366 | 0.0283 | 0.0221 | 0.0176 |
Tinned | 0.100 | 0.0762 | 0.0607 | 0.0475 | 0.0369 | 0.0286 | 0.0224 | 0.0177 | |
Al ( Ω/km) | 0.164 | 0.125 | 0.100 | 0.0778 | 0.0605 | 0.0469 | 0.0367 | 0.0291 |
Approximate size & weight of NA2XBY Al/XLPE/STA/PVC Armoured Underground Power Cable
Two-core of NA2XBY Al/XLPE/STA/PVC Armoured Underground Power Cable
Normal cross-sectional area of conductor | Normal thickness of insulation | Thickness of inner-covering | Thickness of steel tape | Normal thickness of sheath | Approx. overall diameter | Approx. weight |
mm² | mm | mm | mm | mm | mm | kg/km |
2*4 | 0.7 | 1.2 | 0.2 | 1.8 | 15 | 274 |
2*6 | 0.7 | 1.2 | 0.2 | 1.8 | 16 | 314 |
2*10 | 0.7 | 1.2 | 0.2 | 1.8 | 18 | 396 |
2*16 | 0.7 | 1.2 | 0.2 | 1.8 | 20 | 490 |
2*25 | 0.9 | 1.2 | 0.2 | 1.8 | 24 | 645 |
2*35 | 0.9 | 1.2 | 0.2 | 1.8 | 26 | 782 |
2*50 | 1.0 | 1.2 | 0.2 | 1.8 | 24 | 775 |
2*70 | 1.1 | 1.2 | 0.5 | 2.0 | 28 | 1263 |
2*95 | 1.1 | 1.2 | 0.5 | 2.1 | 31 | 1532 |
2*120 | 1.2 | 1.2 | 0.5 | 2.2 | 34 | 1783 |
2*150 | 1.4 | 1.3 | 0.5 | 2.4 | 37 | 2113 |
2*185 | 1.6 | 1.3 | 0.5 | 2.5 | 41 | 2508 |
Three-core of NA2XBY Al/XLPE/STA/PVC Armoured Underground Power Cable
Normal cross-sectional area of conductor | Normal thickness of insulation | Thickness of inner-covering | Thickness of steel tape | Normal thickness of sheath | Approx. overall diameter | Approx. weight |
mm² | mm | mm | mm | mm | mm | kg/km |
3*4 | 0.7 | 1.2 | 0.2 | 1.8 | 15 | 303 |
3*6 | 0.7 | 1.2 | 0.2 | 1.8 | 16 | 352 |
3*10 | 0.7 | 1.2 | 0.2 | 1.8 | 19 | 462 |
3*16 | 0.7 | 1.2 | 0.2 | 1.8 | 21 | 582 |
3*25 | 0.9 | 1.2 | 0.2 | 1.8 | 25 | 766 |
3*35 | 0.9 | 1.2 | 0.2 | 1.8 | 28 | 927 |
3*50 | 1.0 | 1.2 | 0.2 | 1.9 | 28 | 1027 |
3*70 | 1.1 | 1.2 | 0.5 | 2.0 | 33 | 1636 |
3*95 | 1.1 | 1.2 | 0.5 | 2.2 | 36 | 2026 |
3*120 | 1.2 | 1.3 | 0.5 | 2.3 | 39 | 2394 |
3*150 | 1.4 | 1.3 | 0.5 | 2.4 | 43 | 2832 |
3*185 | 1.6 | 1.4 | 0.5 | 2.6 | 48 | 3400 |
3*240 | 1.7 | 1.5 | 0.5 | 2.8 | 53 | 4195 |
3*300 | 1.8 | 1.5 | 0.5 | 2.9 | 58 | 5020 |
3+1 core of NA2XBY Al/XLPE/STA/PVC Armoured Underground Power Cable
Normal cross-sectional area of conductor | Normal thickness of insulation | Thickness of inner-covering | Thickness of steel tape | Normal thickness of sheath | Approx. overall diameter | Approx. weight |
mm² | mm | mm | mm | mm | mm | kg/km |
3*4+1*2.5 | 0.7 | 1.2 | 0.2 | 1.8 | 16 | 333 |
3*6+1*4 | 0.7 | 1.2 | 0.2 | 1.8 | 17 | 388 |
3*10+1*6 | 0.7 | 1.2 | 0.2 | 1.8 | 20 | 503 |
3*16+1*10 | 0.7 | 1.2 | 0.2 | 1.8 | 23 | 650 |
3*25+1*16 | 0.9 | 1.2 | 0.2 | 1.8 | 26 | 856 |
3*35+1*16 | 0.9 | 1.2 | 0.2 | 1.8 | 28 | 994 |
3*50+1*25 | 1.0 | 1.2 | 0.2 | 1.9 | 30 | 1175 |
3*70+1*35 | 1.1 | 1.2 | 0.2 | 2.1 | 35 | 1872 |
3*95+1*50 | 1.1 | 1.2 | 0.2 | 2.2 | 39 | 2303 |
3*120+1*70 | 1.2 | 1.3 | 0.2 | 2.3 | 43 | 2772 |
3*150+1*70 | 1.4 | 1.4 | 0.5 | 2.5 | 47 | 3238 |
3*185+1*95 | 1.6 | 1.5 | 0.5 | 2.6 | 52 | 3908 |
3*240+1*120 | 1.7 | 1.6 | 0.5 | 2.8 | 57 | 4792 |
3*300+1*150 | 1.8 | 1.7 | 0.5 | 3 | 63 | 5747 |
Four-core of NA2XBY Al/XLPE/STA/PVC Armoured Underground Power Cable
Normal cross-sectional area of conductor | Normal thickness of insulation | Thickness of inner-covering | Thickness of steel tape | Normal thickness of sheath | Approx. overall diameter | Approx. weight |
mm² | mm | mm | mm | mm | mm | kg/km |
4*4 | 0.7 | 1.2 | 0.2 | 1.8 | 16 | 408 |
4*6 | 0.7 | 1.2 | 0.2 | 1.8 | 17 | 488 |
4*10 | 0.7 | 1.2 | 0.2 | 1.8 | 21 | 688 |
4*16 | 0.7 | 1.2 | 0.2 | 1.8 | 23 | 927 |
4*25 | 0.9 | 1.2 | 0.2 | 1.8 | 27 | 1267 |
4*35 | 0.9 | 1.2 | 0.2 | 1.8 | 30 | 1558 |
4*50 | 1.0 | 1.2 | 0.2 | 2.0 | 33 | 2136 |
4*70 | 1.1 | 1.2 | 0.5 | 2.1 | 36 | 2485 |
4*95 | 1.1 | 1.2 | 0.5 | 2.3 | 41 | 2813 |
4*120 | 1.2 | 1.3 | 0.5 | 2.4 | 44 | 2945 |
4*150 | 1.4 | 1.4 | 0.5 | 2.4 | 49 | 3533 |
4*185 | 1.6 | 1.5 | 0.5 | 2.7 | 54 | 4236 |
4*240 | 1.7 | 1.6 | 0.5 | 3.0 | 60 | 5625 |
4*300 | 1.8 | 1.7 | 0.5 | 3.1 | 66 | 6286 |
3+2 core of NA2XBY Al/XLPE/STA/PVC Armoured Underground Power Cable
Normal cross-sectional area of conductor | Normal thickness of insulation | Thickness of inner-covering | Thickness of steel tape | Normal thickness of sheath | Approx. overall diameter | Approx. weight |
mm² | mm | mm | mm | mm | mm | kg/km |
3*4+2*1.5 | 0.7 | 1.2 | 0.2 | 1.8 | 17 | 356 |
3*6+2*4 | 0.7 | 1.2 | 0.2 | 1.8 | 18 | 420 |
3*10+2*6 | 0.7 | 1.2 | 0.2 | 1.8 | 21 | 538 |
3*16+2*10 | 0.7 | 1.2 | 0.2 | 1.8 | 24 | 702 |
3*25+2*16 | 0.9 | 1.2 | 0.2 | 1.8 | 27 | 930 |
3*35+2*16 | 0.9 | 1.2 | 0.2 | 1.8 | 29 | 1061 |
3*50+2*25 | 1.0 | 1.2 | 0.5 | 2.0 | 35 | 1770 |
3*70+2*35 | 1.1 | 1.2 | 0.5 | 2.1 | 40 | 2244 |
3*95+2*50 | 1.1 | 1.2 | 0.5 | 2.3 | 44 | 2769 |
3*120+2*70 | 1.2 | 1.3 | 0.5 | 2.4 | 49 | 3269 |
3*150+2*70 | 1.4 | 1.4 | 0.5 | 2.5 | 53 | 3752 |
3*185+2*95 | 1.6 | 1.5 | 0.5 | 2.7 | 59 | 4565 |
3*240+2*120 | 1.7 | 1.6 | 0.5 | 2.9 | 65 | 5635 |
3*300+2*150 | 1.8 | 1.7 | 0.5 | 3.1 | 72 | 6783 |
4+1 core of NA2XBY Al/XLPE/STA/PVC Armoured Underground Power Cable
Normal cross-sectional area of conductor | Normal thickness of insulation | Thickness of inner-covering | Thickness of steel tape | Normal thickness of sheath | Approx. overall diameter | Approx. weight |
mm² | mm | mm | mm | mm | mm | kg/km |
4*4+1*2.5 | 0.7 | 1.2 | 0.2 | 1.8 | 17 | 368 |
4*6+1*4 | 0.7 | 1.2 | 0.2 | 1.8 | 18 | 460 |
4*10+1*6 | 0.7 | 1.2 | 0.2 | 1.8 | 21 | 588 |
4*16+1*10 | 0.7 | 1.2 | 0.2 | 1.8 | 24 | 738 |
4*25+1*16 | 0.9 | 1.2 | 0.2 | 1.8 | 28 | 976 |
4*35+1*16 | 0.9 | 1.2 | 0.2 | 1.8 | 30 | 1169 |
4*50+1*25 | 1.0 | 1.2 | 0.5 | 2.1 | 36 | 1191 |
4*70+1*35 | 1.1 | 1.2 | 0.5 | 2.2 | 41 | 2432 |
4*95+1*50 | 1.1 | 1.2 | 0.5 | 2.3 | 46 | 3004 |
4*120+1*70 | 1.2 | 1.3 | 0.5 | 2.5 | 51 | 3679 |
4*150+1*70 | 1.4 | 1.4 | 0.5 | 2.6 | 55 | 4126 |
4*185+1*95 | 1.6 | 1.5 | 0.5 | 2.8 | 61 | 5029 |
4*240+1*120 | 1.7 | 1.6 | 0.5 | 2.9 | 69 | 6288 |
4*300+1*150 | 1.8 | 1.8 | 0.5 | 3.3 | 76 | 7552 |
5 core of NA2XBY Al/XLPE/STA/PVC Armoured Underground Power Cable
Normal cross-sectional area of conductor | Normal thickness of insulation | Thickness of inner-covering | Thickness of steel tape | Normal thickness of sheath | Approx. overall diameter | Approx. weight |
mm² | mm | mm | mm | mm | mm | kg/km |
5*4 | 0.7 | 1.2 | 0.2 | 1.8 | 17 | 380 |
5*6 | 0.7 | 1.2 | 0.2 | 1.8 | 19 | 448 |
5*10 | 0.7 | 1.2 | 0.2 | 1.8 | 22 | 605 |
5*16 | 0.7 | 1.2 | 0.2 | 1.8 | 25 | 769 |
5*25 | 0.9 | 1.2 | 0.5 | 1.8 | 28 | 1023 |
5*35 | 0.9 | 1.2 | 0.5 | 2.0 | 33 | 1603 |
5*50 | 1.0 | 1.2 | 0.5 | 2.1 | 37 | 2033 |
5*70 | 1.1 | 1.2 | 0.5 | 2.2 | 42 | 2578 |
5*95 | 1.1 | 1.3 | 0.5 | 2.4 | 48 | 3265 |
5*120 | 1.2 | 1.4 | 0.5 | 2.6 | 53 | 3797 |
5*150 | 1.4 | 1.5 | 0.5 | 2.7 | 58 | 4565 |
5*185 | 1.6 | 1.6 | 0.5 | 2.9 | 65 | 5494 |
5*240 | 1.7 | 1.7 | 0.5 | 3.2 | 73 | 6981 |
5*300 | 1.8 | 1.9 | 0.5 | 3.4 | 80 | 8341 |
The power cable current capacity of 0.6/1kV NA2XBY Al/XLPE/STA/PVC Armoured Underground Power Cable
Apply the model number: YJV22(N2XBY) YJLV22(NA2XBY)
Limit the term:Environment temperature:400C;: Soil temperature:250C; Soil thermal receptivity: 2000C·cm/W
Conductor Area mm2 | The long-term admission current-carrying capacity in air(A) | The long-term admission current-carrying capacity in soil(A) | ||||||
Copper core cable | Aluminum core cable | Copper core cable | Aluminum core cable | |||||
1-core | 3 or 4 core | 1-core | 3 or 4 core | 1-core | 3 or 4 core | 1-core | 3 or 4 core | |
2.5 | 34 | 32 | 27 | 25 | 36 | 32 | 27 | 25 |
4 | 44 | 41 | 35 | 32 | 47 | 41 | 35 | 32 |
6 | 56 | 52 | 45 | 42 | 59 | 52 | 46 | 42 |
10 | 77 | 70 | 60 | 53 | 78 | 69 | 59 | 53 |
16 | 100 | 91 | 78 | 70 | 102 | 90 | 77 | 71 |
25 | 132 | 118 | 102 | 91 | 130 | 117 | 104 | 91 |
35 | 164 | 150 | 127 | 114 | 169 | 143 | 117 | 113 |
50 | 196 | 182 | 152 | 146 | 187 | 169 | 139 | 134 |
70 | 251 | 228 | 195 | 178 | 226 | 208 | 174 | 165 |
95 | 305 | 273 | 236 | 214 | 269 | 247 | 208 | 195 |
120 | 351 | 314 | 272 | 246 | 300 | 282 | 239 | 221 |
150 | 401 | 360 | 311 | 278 | 339 | 321 | 269 | 247 |
185 | 461 | 410 | 359 | 319 | 382 | 356 | 300 | 278 |
240 | 546 | 483 | 424 | 378 | 435 | 408 | 348 | 321 |
300 | 611 | 552 | 474 | 419 | 495 | 469 | 391 | 365 |
400 | 716 | / | 546 | / | 574 | / | 456 | / |