0.6/1kV N2XBY CU/XLPE/STA/PVC Power Cable
Introduction of N2XBY Copper Conductor XLPE Insulation Power Cable
XLPE insulated power cables for rated voltages up to 0.6/1 kV are fit for AC 50Hz distribution lines for the same rated voltages. The mechanical and electrical properties of these cables are accordant with GB/T12706—2008 ( Power cables extruded insulation and their accessories of rated voltagesl kV(Umz1.2kV)up to ) and IEC-60502—1 :2004 ( Extruded insulation power cables and appendites for rated voltages 1kV up to 30kV)
Instruction of Application
1. Rated Voltage: 0.6/1kV
2. Max.permissible operating temperature of conductor is 90℃.
3. Conductor short-circuit temperature shall not exceed 250℃ Max. sustaining period shall not exceed 5 seconds.
4. Bending Radius
Bending radius of single core cable:15(D+d)±5%
Bending radius of multi core cable:12(D+d)±5%
D-Actual outer diameter of cable sample(mm);
d-Actual diameter of the conductor(mm).
5. No restriction of level difference along the route for installation.
6. Installation temperature shall be heated when ambient temperature is below 0℃
Production Range of XLPE Insulated Power Cable
Type | Description | Scope of Application |
YJV YJLV Z(K)-YJV Z(K)-YJLV | Cu or AI conductor XLPE insulated PVC sheathed power cable | Installed indoors or outdoors. In case unable to bear external mechanical forces but tractive force during laying, single core cable in magnetic duct is not permissible. |
YJV22 YJLV22 Z(K)-YJV22 Z(K)-YJLV22 | Cu or AI Conductor XLPE Insulated PVC Sheathed Steel Tape Armoured Power Cable | For laying in ground able to bear external mechanical forces, but unable to bear large pulling force. |
YJV32 YJLV32 Z(K)-YJV32 Z(K)-YJLV32 | Cu or AI Conductor XLPE Insulated PVC Sheathed Fine Steel Wire Armoured Power Cable | For laying in water or able to bear external mechanical forces and equal pulling force. |
Structure of N2XRY Copper Conductor XLPE Insulation Power Cable
The main technique performance of N2XBY Copper Conductor XLPE Insulation Power Cable
Maximum DC resistance of cable conductor at 20℃
Rated cross area(mm2) | 0.5 | 0.75 | 1.0 | 1.5 | 2.5 | 4 | 6 | 10 | |
Cu(Ω/km) | Non tinned | 36.0 | 24.5 | 18.1 | 12.1 | 7.41 | 4.61 | 3.08 | 1.83 |
Tinned | 36.7 | 24.8 | 18.2 | 12.2 | 7.56 | 4.70 | 3.11 | 1.84 | |
Al (Ω/km) | / | / | / | 18.1 | 12.1 | 7.41 | 4.61 | 3.08 | |
Rated cross area(mm2) | 16 | 25 | 35 | 50 | 70 | 95 | 120 | 150 | |
Cu (Ω/km) | Non tinned | 1.15 | 0.727 | 0.524 | 0.387 | 0.268 | 0.193 | 0.153 | 0.124 |
Tinned | 1.16 | 0.734 | 0.529 | 0.391 | 0.270 | 0.195 | 0.154 | 0.126 | |
Al (Ω/km) | 1.91 | 1.20 | 0.868 | 0.641 | 0.443 | 0.320 | 0.253 | 0.206 | |
Rated cross area(mm2) | 185 | 240 | 300 | 400 | 500 | 630 | 800 | 1000 | |
Cu (Ω/km) | Non tinned | 0.0991 | 0.0754 | 0.0601 | 0.0470 | 0.0366 | 0.0283 | 0.0221 | 0.0176 |
Tinned | 0.100 | 0.0762 | 0.0607 | 0.0475 | 0.0369 | 0.0286 | 0.0224 | 0.0177 | |
Al ( Ω/km) | 0.164 | 0.125 | 0.100 | 0.0778 | 0.0605 | 0.0469 | 0.0367 | 0.0291 |
Approximate size & weight of N2XBY Copper Conductor XLPE Insulation Power Cable
Two-core of CU/XLPE/STA/PVC Power Cable
Normal cross-sectional area of conductor | Normal thickness of insulation | Thickness of inner-covering | Thickness of steel tape | Normal thickness of sheath | Approx. overall diameter | Approx. weight |
mm² | mm | mm | mm | mm | mm | kg/km |
2*4 | 0.7 | 1.2 | 0.2 | 1.8 | 15 | 324 |
2*6 | 0.7 | 1.2 | 0.2 | 1.8 | 16 | 390 |
2*10 | 0.7 | 1.2 | 0.2 | 1.8 | 18 | 524 |
2*16 | 0.7 | 1.2 | 0.2 | 1.8 | 20 | 694 |
2*25 | 0.9 | 1.2 | 0.2 | 1.8 | 24 | 978 |
2*35 | 0.9 | 1.2 | 0.2 | 1.8 | 26 | 1222 |
2*50 | 1.0 | 1.2 | 0.2 | 1.8 | 24 | 1372 |
2*70 | 1.1 | 1.2 | 0.5 | 2.0 | 28 | 2124 |
2*95 | 1.1 | 1.2 | 0.5 | 2.1 | 31 | 2728 |
2*120 | 1.2 | 1.2 | 0.5 | 2.2 | 34 | 3292 |
2*150 | 1.4 | 1.3 | 0.5 | 2.4 | 37 | 3975 |
2*185 | 1.6 | 1.3 | 0.5 | 2.5 | 41 | 4838 |
Three-core of CU/XLPE/STA/PVC Power Cable
Normal cross-sectional area of conductor | Normal thickness of insulation | Thickness of inner-covering | Thickness of steel tape | Normal thickness of sheath | Approx. overall diameter | Approx. weight |
mm² | mm | mm | mm | mm | mm | kg/km |
3*4 | 0.7 | 1.2 | 0.2 | 1.8 | 15 | 379 |
3*6 | 0.7 | 1.2 | 0.2 | 1.8 | 16 | 466 |
3*10 | 0.7 | 1.2 | 0.2 | 1.8 | 19 | 655 |
3*16 | 0.7 | 1.2 | 0.2 | 1.8 | 21 | 887 |
3*25 | 0.9 | 1.2 | 0.2 | 1.8 | 25 | 1243 |
3*35 | 0.9 | 1.2 | 0.2 | 1.8 | 28 | 1588 |
3*50 | 1.0 | 1.2 | 0.2 | 1.9 | 28 | 1923 |
3*70 | 1.1 | 1.2 | 0.5 | 2.0 | 33 | 2929 |
3*95 | 1.1 | 1.2 | 0.5 | 2.2 | 36 | 3822 |
3*120 | 1.2 | 1.3 | 0.5 | 2.3 | 39 | 4659 |
3*150 | 1.4 | 1.3 | 0.5 | 2.4 | 43 | 5627 |
3*185 | 1.6 | 1.4 | 0.5 | 2.6 | 48 | 6897 |
3*240 | 1.7 | 1.5 | 0.5 | 2.8 | 53 | 8788 |
3*300 | 1.8 | 1.5 | 0.5 | 2.9 | 58 | 10757 |
3+1 core of CU/XLPE/STA/PVC Power Cable
Normal cross-sectional area of conductor | Normal thickness of insulation | Thickness of inner-covering | Thickness of steel tape | Normal thickness of sheath | Approx. overall diameter | Approx. weight |
mm² | mm | mm | mm | mm | mm | kg/km |
3*4+1*2.5 | 0.7 | 1.2 | 0.2 | 1.8 | 16 | 425 |
3*6+1*4 | 0.7 | 1.2 | 0.2 | 1.8 | 17 | 527 |
3*10+1*6 | 0.7 | 1.2 | 0.2 | 1.8 | 20 | 734 |
3*16+1*10 | 0.7 | 1.2 | 0.2 | 1.8 | 23 | 1019 |
3*25+1*16 | 0.9 | 1.2 | 0.2 | 1.8 | 26 | 1434 |
3*35+1*16 | 0.9 | 1.2 | 0.2 | 1.8 | 28 | 1757 |
3*50+1*25 | 1.0 | 1.2 | 0.2 | 1.9 | 30 | 2229 |
3*70+1*35 | 1.1 | 1.2 | 0.2 | 2.1 | 35 | 3386 |
3*95+1*50 | 1.1 | 1.2 | 0.2 | 2.2 | 39 | 4397 |
3*120+1*70 | 1.2 | 1.3 | 0.2 | 2.3 | 43 | 5468 |
3*150+1*70 | 1.4 | 1.4 | 0.5 | 2.5 | 47 | 6464 |
3*185+1*95 | 1.6 | 1.5 | 0.5 | 2.6 | 52 | 8004 |
3*240+1*120 | 1.7 | 1.6 | 0.5 | 2.8 | 57 | 10140 |
3*300+1*150 | 1.8 | 1.7 | 0.5 | 3 | 63 | 12445 |
Four core of CU/XLPE/STA/PVC Power Cable
Normal cross-sectional area of conductor | Normal thickness of insulation | Thickness of inner-covering | Thickness of steel tape | Normal thickness of sheath | Approx. overall diameter | Approx. weight |
mm² | mm | mm | mm | mm | mm | kg/km |
4*4 | 0.7 | 1.2 | 0.2 | 1.8 | 16 | 446 |
4*6 | 0.7 | 1.2 | 0.2 | 1.8 | 17 | 550 |
4*10 | 0.7 | 1.2 | 0.2 | 1.8 | 21 | 787 |
4*16 | 0.7 | 1.2 | 0.2 | 1.8 | 23 | 1076 |
4*25 | 0.9 | 1.2 | 0.2 | 1.8 | 27 | 1519 |
4*35 | 0.9 | 1.2 | 0.2 | 1.8 | 30 | 1957 |
4*50 | 1.0 | 1.2 | 0.2 | 2.0 | 33 | 2759 |
4*70 | 1.1 | 1.2 | 0.5 | 2.1 | 36 | 3678 |
4*95 | 1.1 | 1.2 | 0.5 | 2.3 | 41 | 4832 |
4*120 | 1.2 | 1.3 | 0.5 | 2.4 | 44 | 5906 |
4*150 | 1.4 | 1.4 | 0.5 | 2.4 | 49 | 7186 |
4*185 | 1.6 | 1.5 | 0.5 | 2.7 | 54 | 8807 |
4*240 | 1.7 | 1.6 | 0.5 | 3.0 | 60 | 11268 |
4*300 | 1.8 | 1.7 | 0.5 | 3.1 | 66 | 13824 |
3+2 core of CU/XLPE/STA/PVC Power CableFour-core of CU/XLPE/STA/PVC Power Cable
Normal cross-sectional area of conductor | Normal thickness of insulation | Thickness of inner-covering | Thickness of steel tape | Normal thickness of sheath | Approx. overall diameter | Approx. weight |
mm² | mm | mm | mm | mm | mm | kg/km |
3*4+2*1.5 | 0.7 | 1.2 | 0.2 | 1.8 | 17 | 463 |
3*6+2*4 | 0.7 | 1.2 | 0.2 | 1.8 | 18 | 584 |
3*10+2*6 | 0.7 | 1.2 | 0.2 | 1.8 | 21 | 806 |
3*16+2*10 | 0.7 | 1.2 | 0.2 | 1.8 | 24 | 1136 |
3*25+2*16 | 0.9 | 1.2 | 0.2 | 1.8 | 27 | 1610 |
3*35+2*16 | 0.9 | 1.2 | 0.2 | 1.8 | 29 | 1926 |
3*50+2*25 | 1.0 | 1.2 | 0.5 | 2.0 | 35 | 2983 |
3*70+2*35 | 1.1 | 1.2 | 0.5 | 2.1 | 40 | 3979 |
3*95+2*50 | 1.1 | 1.2 | 0.5 | 2.3 | 44 | 5162 |
3*120+2*70 | 1.2 | 1.3 | 0.5 | 2.4 | 49 | 6397 |
3*150+2*70 | 1.4 | 1.4 | 0.5 | 2.5 | 53 | 7409 |
3*185+2*95 | 1.6 | 1.5 | 0.5 | 2.7 | 59 | 9259 |
3*240+2*120 | 1.7 | 1.6 | 0.5 | 2.9 | 65 | 11737 |
3*300+2*150 | 1.8 | 1.7 | 0.5 | 3.1 | 72 | 14413 |
4+1 core of CU/XLPE/STA/PVC Power Cable
Normal cross-sectional area of conductor | Normal thickness of insulation | Thickness of inner-covering | Thickness of steel tape | Normal thickness of sheath | Approx. overall diameter | Approx. weight |
mm² | mm | mm | mm | mm | mm | kg/km |
4*4+1*2.5 | 0.7 | 1.2 | 0.2 | 1.8 | 17 | 485 |
4*6+1*4 | 0.7 | 1.2 | 0.2 | 1.8 | 18 | 637 |
4*10+1*6 | 0.7 | 1.2 | 0.2 | 1.8 | 21 | 882 |
4*16+1*10 | 0.7 | 1.2 | 0.2 | 1.8 | 24 | 1208 |
4*25+1*16 | 0.9 | 1.2 | 0.2 | 1.8 | 28 | 1713 |
4*35+1*16 | 0.9 | 1.2 | 0.2 | 1.8 | 30 | 2152 |
4*50+1*25 | 1.0 | 1.2 | 0.5 | 2.1 | 36 | 3263 |
4*70+1*35 | 1.1 | 1.2 | 0.5 | 2.2 | 41 | 4367 |
4*95+1*50 | 1.1 | 1.2 | 0.5 | 2.3 | 46 | 5695 |
4*120+1*70 | 1.2 | 1.3 | 0.5 | 2.5 | 51 | 7129 |
4*150+1*70 | 1.4 | 1.4 | 0.5 | 2.6 | 55 | 8282 |
4*185+1*95 | 1.6 | 1.5 | 0.5 | 2.8 | 61 | 10287 |
4*240+1*120 | 1.7 | 1.6 | 0.5 | 2.9 | 69 | 13163 |
4*300+1*150 | 1.8 | 1.8 | 0.5 | 3.3 | 76 | 16169 |
5 core of CU/XLPE/STA/PVC Power Cable
Normal cross-sectional area of conductor | Normal thickness of insulation | Thickness of inner-covering | Thickness of steel tape | Normal thickness of sheath | Approx. overall diameter | Approx. weight |
mm² | mm | mm | mm | mm | mm | kg/km |
5*4 | 0.7 | 1.2 | 0.2 | 1.8 | 17 | 507 |
5*6 | 0.7 | 1.2 | 0.2 | 1.8 | 19 | 638 |
5*10 | 0.7 | 1.2 | 0.2 | 1.8 | 22 | 926 |
5*16 | 0.7 | 1.2 | 0.2 | 1.8 | 25 | 1277 |
5*25 | 0.9 | 1.2 | 0.5 | 1.8 | 28 | 1817 |
5*35 | 0.9 | 1.2 | 0.5 | 2.0 | 33 | 2705 |
5*50 | 1.0 | 1.2 | 0.5 | 2.1 | 37 | 3525 |
5*70 | 1.1 | 1.2 | 0.5 | 2.2 | 42 | 4732 |
5*95 | 1.1 | 1.3 | 0.5 | 2.4 | 48 | 6256 |
5*120 | 1.2 | 1.4 | 0.5 | 2.6 | 53 | 7571 |
5*150 | 1.4 | 1.5 | 0.5 | 2.7 | 58 | 9221 |
5*185 | 1.6 | 1.6 | 0.5 | 2.9 | 65 | 11319 |
5*240 | 1.7 | 1.7 | 0.5 | 3.2 | 73 | 14631 |
5*300 | 1.8 | 1.9 | 0.5 | 3.4 | 80 | 17948 |
The power cable current capacity of 0.6/1kV CU/XLPE/STA/PVC Power Cable
Limit the term:Environment temperature:400C;: Soil temperature:250C; Soil thermal receptivity: 2000C·cm/W
Conductor Area mm2 | The long-term admission current-carrying capacity in air(A) | The long-term admission current-carrying capacity in soil(A) | ||
Copper core cable | Aluminum core cable | Copper core cable | Aluminum core cable | |
3 or 4 core | 3 or 4 core | 3 or 4 core | 3 or 4 core | |
4 | 41 | 32 | 41 | 32 |
6 | 52 | 42 | 52 | 42 |
10 | 70 | 53 | 69 | 53 |
16 | 91 | 70 | 90 | 71 |
25 | 118 | 91 | 117 | 91 |
35 | 150 | 114 | 143 | 113 |
50 | 182 | 146 | 169 | 134 |
70 | 228 | 178 | 208 | 165 |
95 | 273 | 214 | 247 | 195 |
120 | 314 | 246 | 282 | 221 |
150 | 360 | 278 | 321 | 247 |
185 | 410 | 319 | 356 | 278 |
240 | 483 | 378 | 408 | 321 |
300 | 552 | 419 | 469 | 365 |
0.6/1kV N2XBY CU/XLPE/STA/PVC Power Cable
Introduction of N2XBY Copper Conductor XLPE Insulation Power Cable
XLPE insulated power cables for rated voltages up to 0.6/1 kV are fit for AC 50Hz distribution lines for the same rated voltages. The mechanical and electrical properties of these cables are accordant with GB/T12706—2008 ( Power cables extruded insulation and their accessories of rated voltagesl kV(Umz1.2kV)up to ) and IEC-60502—1 :2004 ( Extruded insulation power cables and appendites for rated voltages 1kV up to 30kV)
Instruction of Application
1. Rated Voltage: 0.6/1kV
2. Max.permissible operating temperature of conductor is 90℃.
3. Conductor short-circuit temperature shall not exceed 250℃ Max. sustaining period shall not exceed 5 seconds.
4. Bending Radius
Bending radius of single core cable:15(D+d)±5%
Bending radius of multi core cable:12(D+d)±5%
D-Actual outer diameter of cable sample(mm);
d-Actual diameter of the conductor(mm).
5. No restriction of level difference along the route for installation.
6. Installation temperature shall be heated when ambient temperature is below 0℃
Production Range of XLPE Insulated Power Cable
Type | Description | Scope of Application |
YJV YJLV Z(K)-YJV Z(K)-YJLV | Cu or AI conductor XLPE insulated PVC sheathed power cable | Installed indoors or outdoors. In case unable to bear external mechanical forces but tractive force during laying, single core cable in magnetic duct is not permissible. |
YJV22 YJLV22 Z(K)-YJV22 Z(K)-YJLV22 | Cu or AI Conductor XLPE Insulated PVC Sheathed Steel Tape Armoured Power Cable | For laying in ground able to bear external mechanical forces, but unable to bear large pulling force. |
YJV32 YJLV32 Z(K)-YJV32 Z(K)-YJLV32 | Cu or AI Conductor XLPE Insulated PVC Sheathed Fine Steel Wire Armoured Power Cable | For laying in water or able to bear external mechanical forces and equal pulling force. |
Structure of N2XRY Copper Conductor XLPE Insulation Power Cable
The main technique performance of N2XBY Copper Conductor XLPE Insulation Power Cable
Maximum DC resistance of cable conductor at 20℃
Rated cross area(mm2) | 0.5 | 0.75 | 1.0 | 1.5 | 2.5 | 4 | 6 | 10 | |
Cu(Ω/km) | Non tinned | 36.0 | 24.5 | 18.1 | 12.1 | 7.41 | 4.61 | 3.08 | 1.83 |
Tinned | 36.7 | 24.8 | 18.2 | 12.2 | 7.56 | 4.70 | 3.11 | 1.84 | |
Al (Ω/km) | / | / | / | 18.1 | 12.1 | 7.41 | 4.61 | 3.08 | |
Rated cross area(mm2) | 16 | 25 | 35 | 50 | 70 | 95 | 120 | 150 | |
Cu (Ω/km) | Non tinned | 1.15 | 0.727 | 0.524 | 0.387 | 0.268 | 0.193 | 0.153 | 0.124 |
Tinned | 1.16 | 0.734 | 0.529 | 0.391 | 0.270 | 0.195 | 0.154 | 0.126 | |
Al (Ω/km) | 1.91 | 1.20 | 0.868 | 0.641 | 0.443 | 0.320 | 0.253 | 0.206 | |
Rated cross area(mm2) | 185 | 240 | 300 | 400 | 500 | 630 | 800 | 1000 | |
Cu (Ω/km) | Non tinned | 0.0991 | 0.0754 | 0.0601 | 0.0470 | 0.0366 | 0.0283 | 0.0221 | 0.0176 |
Tinned | 0.100 | 0.0762 | 0.0607 | 0.0475 | 0.0369 | 0.0286 | 0.0224 | 0.0177 | |
Al ( Ω/km) | 0.164 | 0.125 | 0.100 | 0.0778 | 0.0605 | 0.0469 | 0.0367 | 0.0291 |
Approximate size & weight of N2XBY Copper Conductor XLPE Insulation Power Cable
Two-core of CU/XLPE/STA/PVC Power Cable
Normal cross-sectional area of conductor | Normal thickness of insulation | Thickness of inner-covering | Thickness of steel tape | Normal thickness of sheath | Approx. overall diameter | Approx. weight |
mm² | mm | mm | mm | mm | mm | kg/km |
2*4 | 0.7 | 1.2 | 0.2 | 1.8 | 15 | 324 |
2*6 | 0.7 | 1.2 | 0.2 | 1.8 | 16 | 390 |
2*10 | 0.7 | 1.2 | 0.2 | 1.8 | 18 | 524 |
2*16 | 0.7 | 1.2 | 0.2 | 1.8 | 20 | 694 |
2*25 | 0.9 | 1.2 | 0.2 | 1.8 | 24 | 978 |
2*35 | 0.9 | 1.2 | 0.2 | 1.8 | 26 | 1222 |
2*50 | 1.0 | 1.2 | 0.2 | 1.8 | 24 | 1372 |
2*70 | 1.1 | 1.2 | 0.5 | 2.0 | 28 | 2124 |
2*95 | 1.1 | 1.2 | 0.5 | 2.1 | 31 | 2728 |
2*120 | 1.2 | 1.2 | 0.5 | 2.2 | 34 | 3292 |
2*150 | 1.4 | 1.3 | 0.5 | 2.4 | 37 | 3975 |
2*185 | 1.6 | 1.3 | 0.5 | 2.5 | 41 | 4838 |
Three-core of CU/XLPE/STA/PVC Power Cable
Normal cross-sectional area of conductor | Normal thickness of insulation | Thickness of inner-covering | Thickness of steel tape | Normal thickness of sheath | Approx. overall diameter | Approx. weight |
mm² | mm | mm | mm | mm | mm | kg/km |
3*4 | 0.7 | 1.2 | 0.2 | 1.8 | 15 | 379 |
3*6 | 0.7 | 1.2 | 0.2 | 1.8 | 16 | 466 |
3*10 | 0.7 | 1.2 | 0.2 | 1.8 | 19 | 655 |
3*16 | 0.7 | 1.2 | 0.2 | 1.8 | 21 | 887 |
3*25 | 0.9 | 1.2 | 0.2 | 1.8 | 25 | 1243 |
3*35 | 0.9 | 1.2 | 0.2 | 1.8 | 28 | 1588 |
3*50 | 1.0 | 1.2 | 0.2 | 1.9 | 28 | 1923 |
3*70 | 1.1 | 1.2 | 0.5 | 2.0 | 33 | 2929 |
3*95 | 1.1 | 1.2 | 0.5 | 2.2 | 36 | 3822 |
3*120 | 1.2 | 1.3 | 0.5 | 2.3 | 39 | 4659 |
3*150 | 1.4 | 1.3 | 0.5 | 2.4 | 43 | 5627 |
3*185 | 1.6 | 1.4 | 0.5 | 2.6 | 48 | 6897 |
3*240 | 1.7 | 1.5 | 0.5 | 2.8 | 53 | 8788 |
3*300 | 1.8 | 1.5 | 0.5 | 2.9 | 58 | 10757 |
3+1 core of CU/XLPE/STA/PVC Power Cable
Normal cross-sectional area of conductor | Normal thickness of insulation | Thickness of inner-covering | Thickness of steel tape | Normal thickness of sheath | Approx. overall diameter | Approx. weight |
mm² | mm | mm | mm | mm | mm | kg/km |
3*4+1*2.5 | 0.7 | 1.2 | 0.2 | 1.8 | 16 | 425 |
3*6+1*4 | 0.7 | 1.2 | 0.2 | 1.8 | 17 | 527 |
3*10+1*6 | 0.7 | 1.2 | 0.2 | 1.8 | 20 | 734 |
3*16+1*10 | 0.7 | 1.2 | 0.2 | 1.8 | 23 | 1019 |
3*25+1*16 | 0.9 | 1.2 | 0.2 | 1.8 | 26 | 1434 |
3*35+1*16 | 0.9 | 1.2 | 0.2 | 1.8 | 28 | 1757 |
3*50+1*25 | 1.0 | 1.2 | 0.2 | 1.9 | 30 | 2229 |
3*70+1*35 | 1.1 | 1.2 | 0.2 | 2.1 | 35 | 3386 |
3*95+1*50 | 1.1 | 1.2 | 0.2 | 2.2 | 39 | 4397 |
3*120+1*70 | 1.2 | 1.3 | 0.2 | 2.3 | 43 | 5468 |
3*150+1*70 | 1.4 | 1.4 | 0.5 | 2.5 | 47 | 6464 |
3*185+1*95 | 1.6 | 1.5 | 0.5 | 2.6 | 52 | 8004 |
3*240+1*120 | 1.7 | 1.6 | 0.5 | 2.8 | 57 | 10140 |
3*300+1*150 | 1.8 | 1.7 | 0.5 | 3 | 63 | 12445 |
Four core of CU/XLPE/STA/PVC Power Cable
Normal cross-sectional area of conductor | Normal thickness of insulation | Thickness of inner-covering | Thickness of steel tape | Normal thickness of sheath | Approx. overall diameter | Approx. weight |
mm² | mm | mm | mm | mm | mm | kg/km |
4*4 | 0.7 | 1.2 | 0.2 | 1.8 | 16 | 446 |
4*6 | 0.7 | 1.2 | 0.2 | 1.8 | 17 | 550 |
4*10 | 0.7 | 1.2 | 0.2 | 1.8 | 21 | 787 |
4*16 | 0.7 | 1.2 | 0.2 | 1.8 | 23 | 1076 |
4*25 | 0.9 | 1.2 | 0.2 | 1.8 | 27 | 1519 |
4*35 | 0.9 | 1.2 | 0.2 | 1.8 | 30 | 1957 |
4*50 | 1.0 | 1.2 | 0.2 | 2.0 | 33 | 2759 |
4*70 | 1.1 | 1.2 | 0.5 | 2.1 | 36 | 3678 |
4*95 | 1.1 | 1.2 | 0.5 | 2.3 | 41 | 4832 |
4*120 | 1.2 | 1.3 | 0.5 | 2.4 | 44 | 5906 |
4*150 | 1.4 | 1.4 | 0.5 | 2.4 | 49 | 7186 |
4*185 | 1.6 | 1.5 | 0.5 | 2.7 | 54 | 8807 |
4*240 | 1.7 | 1.6 | 0.5 | 3.0 | 60 | 11268 |
4*300 | 1.8 | 1.7 | 0.5 | 3.1 | 66 | 13824 |
3+2 core of CU/XLPE/STA/PVC Power CableFour-core of CU/XLPE/STA/PVC Power Cable
Normal cross-sectional area of conductor | Normal thickness of insulation | Thickness of inner-covering | Thickness of steel tape | Normal thickness of sheath | Approx. overall diameter | Approx. weight |
mm² | mm | mm | mm | mm | mm | kg/km |
3*4+2*1.5 | 0.7 | 1.2 | 0.2 | 1.8 | 17 | 463 |
3*6+2*4 | 0.7 | 1.2 | 0.2 | 1.8 | 18 | 584 |
3*10+2*6 | 0.7 | 1.2 | 0.2 | 1.8 | 21 | 806 |
3*16+2*10 | 0.7 | 1.2 | 0.2 | 1.8 | 24 | 1136 |
3*25+2*16 | 0.9 | 1.2 | 0.2 | 1.8 | 27 | 1610 |
3*35+2*16 | 0.9 | 1.2 | 0.2 | 1.8 | 29 | 1926 |
3*50+2*25 | 1.0 | 1.2 | 0.5 | 2.0 | 35 | 2983 |
3*70+2*35 | 1.1 | 1.2 | 0.5 | 2.1 | 40 | 3979 |
3*95+2*50 | 1.1 | 1.2 | 0.5 | 2.3 | 44 | 5162 |
3*120+2*70 | 1.2 | 1.3 | 0.5 | 2.4 | 49 | 6397 |
3*150+2*70 | 1.4 | 1.4 | 0.5 | 2.5 | 53 | 7409 |
3*185+2*95 | 1.6 | 1.5 | 0.5 | 2.7 | 59 | 9259 |
3*240+2*120 | 1.7 | 1.6 | 0.5 | 2.9 | 65 | 11737 |
3*300+2*150 | 1.8 | 1.7 | 0.5 | 3.1 | 72 | 14413 |
4+1 core of CU/XLPE/STA/PVC Power Cable
Normal cross-sectional area of conductor | Normal thickness of insulation | Thickness of inner-covering | Thickness of steel tape | Normal thickness of sheath | Approx. overall diameter | Approx. weight |
mm² | mm | mm | mm | mm | mm | kg/km |
4*4+1*2.5 | 0.7 | 1.2 | 0.2 | 1.8 | 17 | 485 |
4*6+1*4 | 0.7 | 1.2 | 0.2 | 1.8 | 18 | 637 |
4*10+1*6 | 0.7 | 1.2 | 0.2 | 1.8 | 21 | 882 |
4*16+1*10 | 0.7 | 1.2 | 0.2 | 1.8 | 24 | 1208 |
4*25+1*16 | 0.9 | 1.2 | 0.2 | 1.8 | 28 | 1713 |
4*35+1*16 | 0.9 | 1.2 | 0.2 | 1.8 | 30 | 2152 |
4*50+1*25 | 1.0 | 1.2 | 0.5 | 2.1 | 36 | 3263 |
4*70+1*35 | 1.1 | 1.2 | 0.5 | 2.2 | 41 | 4367 |
4*95+1*50 | 1.1 | 1.2 | 0.5 | 2.3 | 46 | 5695 |
4*120+1*70 | 1.2 | 1.3 | 0.5 | 2.5 | 51 | 7129 |
4*150+1*70 | 1.4 | 1.4 | 0.5 | 2.6 | 55 | 8282 |
4*185+1*95 | 1.6 | 1.5 | 0.5 | 2.8 | 61 | 10287 |
4*240+1*120 | 1.7 | 1.6 | 0.5 | 2.9 | 69 | 13163 |
4*300+1*150 | 1.8 | 1.8 | 0.5 | 3.3 | 76 | 16169 |
5 core of CU/XLPE/STA/PVC Power Cable
Normal cross-sectional area of conductor | Normal thickness of insulation | Thickness of inner-covering | Thickness of steel tape | Normal thickness of sheath | Approx. overall diameter | Approx. weight |
mm² | mm | mm | mm | mm | mm | kg/km |
5*4 | 0.7 | 1.2 | 0.2 | 1.8 | 17 | 507 |
5*6 | 0.7 | 1.2 | 0.2 | 1.8 | 19 | 638 |
5*10 | 0.7 | 1.2 | 0.2 | 1.8 | 22 | 926 |
5*16 | 0.7 | 1.2 | 0.2 | 1.8 | 25 | 1277 |
5*25 | 0.9 | 1.2 | 0.5 | 1.8 | 28 | 1817 |
5*35 | 0.9 | 1.2 | 0.5 | 2.0 | 33 | 2705 |
5*50 | 1.0 | 1.2 | 0.5 | 2.1 | 37 | 3525 |
5*70 | 1.1 | 1.2 | 0.5 | 2.2 | 42 | 4732 |
5*95 | 1.1 | 1.3 | 0.5 | 2.4 | 48 | 6256 |
5*120 | 1.2 | 1.4 | 0.5 | 2.6 | 53 | 7571 |
5*150 | 1.4 | 1.5 | 0.5 | 2.7 | 58 | 9221 |
5*185 | 1.6 | 1.6 | 0.5 | 2.9 | 65 | 11319 |
5*240 | 1.7 | 1.7 | 0.5 | 3.2 | 73 | 14631 |
5*300 | 1.8 | 1.9 | 0.5 | 3.4 | 80 | 17948 |
The power cable current capacity of 0.6/1kV CU/XLPE/STA/PVC Power Cable
Limit the term:Environment temperature:400C;: Soil temperature:250C; Soil thermal receptivity: 2000C·cm/W
Conductor Area mm2 | The long-term admission current-carrying capacity in air(A) | The long-term admission current-carrying capacity in soil(A) | ||
Copper core cable | Aluminum core cable | Copper core cable | Aluminum core cable | |
3 or 4 core | 3 or 4 core | 3 or 4 core | 3 or 4 core | |
4 | 41 | 32 | 41 | 32 |
6 | 52 | 42 | 52 | 42 |
10 | 70 | 53 | 69 | 53 |
16 | 91 | 70 | 90 | 71 |
25 | 118 | 91 | 117 | 91 |
35 | 150 | 114 | 143 | 113 |
50 | 182 | 146 | 169 | 134 |
70 | 228 | 178 | 208 | 165 |
95 | 273 | 214 | 247 | 195 |
120 | 314 | 246 | 282 | 221 |
150 | 360 | 278 | 321 | 247 |
185 | 410 | 319 | 356 | 278 |
240 | 483 | 378 | 408 | 321 |
300 | 552 | 419 | 469 | 365 |