Crab 4 AWG AAC Phase + AAAC- Reduced Size Bare Neutral - Triplex Service Drop - PE/XLPE Insulation - Volts 0.6/1kV

ItemTechnical and Specification Sheet - Physical and Electrical Properties Table
Code WordCrab
Phase Conductor typeAAC
Phase Conductor size - AWG / kcmil4
Phase Conductor Number of Wires7
Phase Insulation Thickness0.045 inch or 1.143 mm
Approx Cable Overall Diameter0.61 inch or 15.494 mm
Neutral Conductor typeAAAC- Reduced Size
Neutral Conductor size - AWG / kcmil30.58
Neutral Conductor Number of Wires7
Bare Neutral Rated Strength1110 lbs or 4.93 kN
Conductor Weight (Phase+Neutral)107 lbs/1000ft or 159.22 kg/km
Total Weight143 lbs/1000ft or 212.79 kg/km
Ampacity (PE Covered)115
Ampacity (XLPE Covered)145


Note:


Dimensions and weights not designated minimum or maximum are nominal values and subject to manufacturing tolerances.

Electricity Properties are based on theory calculation, values are subject to final production test results.